An office tower,
tuned from its
own data.
A downtown Calgary office tower, optimized through our Q-Optimization platform. We read the building's data, ran fault detection and diagnostics on it, and gave the operator one short checklist. Nothing was bought and nothing was replaced.












Easy on the
building team.
The operator's part was one checklist of fifteen items. All fifteen were answered the day it was sent. Everything else ran on the platform, where the owner and the operator could follow each step.
- 01ConnectRead-only access to the control system, the utility bills and the last energy audit. Nothing is installed.
- 02Collect21 control points recorded every 10 minutes: fans, schedules, setpoints, boilers, chiller.
- 03DetectFault detection and diagnostics (FDD) checks the data against a library of 17 rules.
- 04DecideOur engineers turn what matters into findings, each with a dollar value and a plain instruction.
- 05ApplyThe operator answers each item: applied, will apply by a date, or not now. No site shutdown.
- 06VerifyEach change is confirmed in the trend data, then counted. Savings are measured, not assumed.
Three settings,
most of the saving.
Eight findings in all. Three of them carry the dollars, and each is a setting the operator can change from the control system's front end.
Fans started at 04:30. People arrive after 06:00.
The air handler schedule moved from 04:30–18:30 to 06:00–18:00. The trend shows 12 running hours per weekday where there were 14, on every weekday since the change.
Supply fans held at full speed.
The duct static pressure setpoint was fixed at 325 Pa, so the fans never slowed down. It is being lowered in steps, then reset on demand.
Boilers firing in warm weather.
The heating plant ran for 220 of the 302 hours recorded above 16 °C outside. A warm-weather lockout is on file for the operator to take up when it suits the plant.

What FDD
added.
The rule library was run again after the review. In one two-week run it flagged three boilers starting far more often than they should, a wear problem that no utility bill shows. It also closed a comfort fault on two floors once the readings came back into range, without anyone having to chase it.

A return with
no capital behind it.
$51,192 a year against an energy bill of about $528,000, from changes that cost nothing to make. The first $20,385 was in the trend data eight weeks after recording began.
| Where it stands | Per year |
|---|---|
| Applied and verified in the trend | $20,385 |
| Agreed with the operator, dated | $23,012 |
| Identified, for later consideration | $7,795 |
| Total found | $51,192 |
- No new equipment and no capital request
- One checklist for the operator, answered in a day
- Every saving tied to a change seen in the building's own data
- The rules run again on new data, so a setting that drifts back shows up
The building, its owner and its people are not named. Figures are as recorded on the Q-Optimization platform in November 2026. "Measured" means the change was seen in the trend data and the saving calculated from it; "agreed" and "identified" amounts are engineering estimates until they are verified the same way. Study fees are not shown.
See what your
building's data says.
Read-only access and a few weeks of trends are enough to start.
Thirty minutes, with the engineer who would run the work.
No cost and no obligation. Bring twelve months of utility bills if you have them — that alone is usually enough to say whether a building has a capital problem or a controls problem.